I-7231D
I-7231D Image
This image is representative of the product and may not be the exact image of this product.
Model: I-7231D
Manufacturer: ICP DAS
CANopen/DCON Master Gateway
Product Status: Active - Active products are produced on a regular manufacturing schedule and are actively supported products. Active products are not necessarily in stock in the USA. Lead time to ship date for Active products is typically stock to 15 business days ARO.

Stock Status: Call

Get Quote ->
DCON protocol is a kind of application protocol based on the RS-485 network. It is special for ICPDAS DCON I/O modules, such as I-7000 series and I-87K series modules. By way of using I-7231D to convert the electric signals and messages, the DCON I/O modules can be upgraded to the CANopen protocol based on the CAN bus. For CANopen protocol application, the I-7231D is a CANopen slave device. So, it can produce or consume the PDO messages, receive the SDO message with proper responses, and deal with the NMT messages from NMT master. For DCON protocol application, it is a DCON master device, and it will collect all of the I/O situations of the I-7000 and I-87K series modules connected with the RS-485 port of I-7231D. Therefore, If the I-7231D receives the command form CAN bus, it does the corresponding reactions for DCON I/O channels. In addition, we also provide the utility tool for users to configure the device parameters and build EDS file for the CANopen slave device. Therefore, users can easily apply I-7k and I-87K IO modules in any CANopen master interface with EDS file via the I-7231D.

Features

  • NMT: Slave
  • Error Control Heart beat or Node Guarding selectable
  • Node ID: Hardware rotary switch
  • No. of PDOs: 16 Rx, 16Tx
  • PDO Modes: Event-triggered, remotely requested, cyclic and acyclic SYNC
  • PDO Mapping: variable
  • No of SDOs: 1 server, 0 client
  • Emergency Message: Yes
  • CANopen Version: DS-301 v4.01
  • Device Profile DSP-401 v2.0
  • Produce EDS file dynamically
  • Baud Rate setting by rotary switch: 10K, 20K, 50K, 125K, 250K, 500K, 800K and 1M bps
  • CAN, ERR and Tx/Rx LED indicators
  • Support max 15 I-7000/I-87K I/O series modules
  • Provide friendly Utility to configure
  • 7-segmemt LED to show operation mode, Node ID, CAN baud and RS-485 baud

Specifications

  • CPU: 80186, 80MHz
  • Philip SJA1000 CAN controller
  • Philip 82C250 CAN transceiver
  • SRAM: 512K bytes
  • Flash Memory: 512K bytes
  • EEPROM: 2k bytes (Can up to 128K bytes or change to 2K/8K FRAM)
  • Real Time Clock
  • Built-in Dual-Watchdog
  • 16-bit Timer
  • 2500 Vrms isolation on CAN side
  • Power Supply: 20W Unregulated +10VDC to +30VDC
  • Operating Temperature: -25 C to +75 C
  • Storage Temperature: -30 C to +85 C
  • Humidity: 5%~95%
  • NS, MS and IO Led directors
  • 7-segmemt LED: 5-digit
  • COM1
    • RS-232
    • RS-232: TXD, RXD, RTS, CTS, GND
    • Communication speed: 115200 max.
    • Configure tool connection
  • COM2
    • RS-485: D2+, D2-
    • Communication speed: 115200 max.
    • Connect to DCON IO modules