SADCC-100
SADCC-100 Image
This image is representative of the product and may not be the exact image of this product.
Model: SADCC-100
Manufacturer: Uptime devices
100' Dry Contact Cable
Product Status: Active - Active products are produced on a regular manufacturing schedule and are actively supported products. Active products are not necessarily in stock in the USA. Lead time to ship date for Active products is typically stock to 15 business days ARO.

Stock Status: Call

Price: $98.75

Features

  • Measurement Range: Alarm/ Normal.
  • Measurement Rate: One reading each second.
  • Communications Cable: RJ-45 to sensor using 15, 60, or 100 foot Helix High Temperature Cable, Maximum extension cable length 305m (1000 ft.) with approved low capacitance shielded cable or UTP.
  • Sensor Disconnection Detection: Yes, using second contact.
  • Sensor Power: Onboard dry contact relays, no power required.
  • Trap Information: Alarm- Sensor Number, Sensor Description, Error/Normal.
  • Input: Every switch has a pull-up resistor settable under snmp control. When used as an input the internal pull-up resistor can be turned on and a normal state configured. The input pin can then sense whether a switch is open or closed by the completion or interruption of the circuit.
  • Output: Every pin can sink 20mA.
  • Reboot: All settings are saved to EPROM memory. During the reboot period all I/O pins are tristate until they are set to their previous value under program control. All spurious signals are disabled during reboot.
  • A/D Converters: Four 10-bit A/D converters. Each A/D is a successive approximation ADC. The ADC contains a sample and hold amplifier, which ensures that the input voltage to the ADC is held to a constant, level during conversion.
  • A/D Converter Accuracy: ±2 LSB.
  • A/D Conversion Time: 280uSec.
  • A/D Integral Non-Linearity: 0.5 LSB.