This image is representative of the product and may not be the exact image of this product.
| Model: CIO-SSH16 |
Manufacturer: Measurement computing | 16 Ch Simultaneous S&H 4Ch Installed
|
Product Status: Special Order - Special Order, Non-Cancellable / Non-Returnable (NCNR)- may be subject to extended lead time and / or minimum order. Stock Status: Call |
|
Get Quote -> |
|
|
|
Features:
Features:
- Adds simultaneous sample & hold front end to A/D board
- 4 channels standard, expandable to 16 channels
- Compatible with CIO-DAS1600, -DAS1400 and -DAS16 families
Analog Input Specifications:
Aperture time: 175nS avg, 250nS max
Aperture uncertainty: ±25 nS
Acquisition time: 4 uS
Max sample rate: 250 KHz
Droop rate: ±100 uV/mS
Input gains: 1, 10, 100, 200, 300, 500, 600, 700 and 800
Gain selection: Switch selectable. Channels may be at different gains.
Accuracy: 0.01% ±1-bit
Additional Channels:
The standard CIO-SSH16 contains 4 channels. Additional channels may be added by purchasing/installing the CIO-SSH-AMP part. Each SSH-AMP adds one channel. The board may contain up to 16 channels.
**Ordering Information**
CIO-SSH-16: 4 channel SSH board
CIO-SSH-AMP: 1 channel expansion (you may add up to 12 channels)
Software Description:
Includes InstaCal ® , installation, calibration and test software. The CIO-SSH16 is supported by the UniversalLibrary ® for use with the DAS-16, DAS-1600 and DAS-1400 families. Also supported by many third party, high-level data acq. programs.
|